Vibration Absorbers

Packless vibration absorbers are designed for installation in the suction and discharge lines of air conditioning and refrigeration systems to dampen the transmission of compressor induced vibration through system piping.

Packless vibration absorbers are recognized under the component programs of Underwriter's Laboratories for application on both refrigerant suction and discharge lines.

Packless vibration absorbers are compatible with all CO2, HC, HFO, HFC, HCFC and CFC refrigerants.

Read More →

Stainless Steel VAFS Models

The Packless VAFS line of improved vibration absorbers are electrically welded without braze joints for improved strength and reliability. They are designed for use with modern high pressure refrigerants. All VAFS vibration absorbers are manufactured with stainless steel flexible tubing and braids.

Model ━ Connection (ID) ▲ Length ━ Working Pressure Burst Pressure
VAFS-3 38 in    9.5 mm 8 14 in    209.6 mm 650 psig    45 bar 3250 psig    224 bar
VAFS-4 12 in    12.7 mm 9 in    228.6 mm 650 psig    45 bar 3250 psig    224 bar
VAFS-5 58 in    15.9 mm 9 34 in    247.7 mm 650 psig    45 bar 3250 psig    224 bar
VAFS-6 34 in    19.1 mm 10 12 in    266.7 mm 650 psig    45 bar 3250 psig    224 bar
VAFS-7 34 in    19.1 mm 11 14 in    285.8 mm 650 psig    45 bar 3250 psig    224 bar
VAFS-8 78 in    22.2 mm 11 12 in    292.1 mm 650 psig    45 bar 3250 psig    224 bar
VAFS-9 1 18 in    28.6 mm 13 in    330.2 mm 650 psig    45 bar 3250 psig    224 bar
VAFS-10 1 38 in    34.9 mm 14 34 in    374.7 mm 650 psig    45 bar 3250 psig    224 bar
VAFS-11 1 58 in    41.3 mm 17 in    431.8 mm 650 psig    45 bar 3250 psig    224 bar
VAFS-12 2 18 in    54.0 mm 20 in    508.0 mm 650 psig    45 bar 3250 psig    224 bar
VAFS-13 2 58 in    66.7 mm 24 in    609.6 mm 460 psig    32 bar 2300 psig    159 bar
VAFS-14 3 18 in    79.4 mm 27 in    685.8 mm 380 psig    26 bar 1900 psig    131 bar

Brass VAF Models

The Packless classic VAF models have a proven track record for quality and reliability. The VAF standard sizes are manufactured with red brass flexible tubing and bronze braids.

Model ━ Connection (ID) ▲ Length ━ Working Pressure Burst Pressure
VAF-1 14 in    6.4 mm 7 in    177.8 mm 660 psig    46 bar 3300 psig    228 bar
VAF-2 14 in    6.4 mm 7 12 in    190.5 mm 660 psig    46 bar 3300 psig    228 bar
VAF-3 38 in    9.5 mm 8 14 in    209.6 mm 620 psig    43 bar 3100 psig    214 bar
VAF-4 12 in    12.7 mm 9 in    228.6 mm 620 psig    43 bar 3100 psig    214 bar
VAF-5 58 in    15.9 mm 9 34 in    247.7 mm 620 psig    43 bar 3100 psig    214 bar
VAF-6 34 in    19.1 mm 10 in    254.0 mm 620 psig    43 bar 3100 psig    214 bar
VAF-7 34 in    19.1 mm 11 14 in    285.8 mm 620 psig    43 bar 3100 psig    214 bar
VAF-8 78 in    22.2 mm 11 12 in    292.1 mm 620 psig    43 bar 3100 psig    214 bar
VAF-9 1 18 in    28.6 mm 13 in    330.2 mm 540 psig    37 bar 2700 psig    186 bar
VAF-10 1 38 in    34.9 mm 14 34 in    374.7 mm 540 psig    37 bar 2700 psig    186 bar
VAF-11 1 58 in    41.3 mm 17 in    431.8 mm 500 psig    34 bar 2500 psig    172 bar

Technical Details

Packless vibration absorbers are constructed with deep pitch corrugated tubing for increased flexibility and vibration absorption. They are covered by high tensile wire braid for superior strength and durability. The vibration absorbers have female copper ends for making sweat connections to refrigerant piping.

Each vibration absorber is pressure tested and then carefully vacuum tested using a sensitive helium mass spectrometer leak detection device. Each units is cleaned, dehydrated and sealed in plastic film after final inspection to ensure cleanliness and dryness prior to installation. Packless vibration absorbers can be purchased in bulk or individually boxed.

Packless can customize the length and type of end connections for the vibration absorber for the specific needs of your application. Contact us today to discuss how we can assist with your requirements.

Installation Notes

VAF Installation
  • Install as close to the compressor or vibration source as possible.
  • Always install perpendicular to the major axis of vibration.
  • Anchor the refrigerant line or piping to a solid member near the end of the vibration absorber furthest from the vibration source (see diagram).
  • Ensure there is sufficient space to minimize static compression and tension of the vibration absorber after soldering.
  • Only install vibration absorbers in a straight line; they are not designed to compensate for offset piping.
  • With VAF models, be careful when making the sweat connection to avoid disturbing the braze joints which have a melting point of 1625 °F.
  • Always direct torch flames away from the body of the vibration absorber (and away from your own body).
  • Clean excess flux or other chemicals from the unit to prevent corrosion.
  • Never use chlorides with the stainless steal VAFS models. Chlorides can cause corrosion and failure of the vibration absorber.