COAX-2100-T

Condenser Coil

The Packless COAX-2100-T coil is designed for 1 ton systems. Packless condenser and water-source heat pump coils provide efficient heat transfer while minimizing fouling. This coil is a part of our classic product line.

← View all Condenser Coils

Condenser Diagram

Specifications

Model COAX-2100-T
Capacity 1 ton
Outer Shell Carbon Steel
Inner Tube Copper
Overall Length 22 916 in
Overall Width 7 in
Overall Height 1 78 in
Dimension A (See Drawing) 6 in
Dimension B (See Drawing) 1 58 in
Dimension C (See Drawing) 78 in
Refrigerant Inlet Connection 38 in (ID)
Refrigerant Outlet Connection 38 in (ID)
Water Inlet Connection 12 in (OD)
Water Outlet Connection 12 in (OD)
Maximum Refrigerant
Working Pressure
650 psig
Maximum Water
Working Pressure
500 psig